Fire System Services

Home : Introduction : FAQ's : Contact Us : Terms & Conditions : Disclaimer
Automatic Fire Suppression Systems : Bush Fire Fighting Equipment : Cylinder Testing : Exit & Emergency Lighting
Fire Extinguishers : Fire Extinguisher Training : Fire Hose Reels : Fire Regulations : Fire Safety : Fire & Smoke Detection
Rechargeable Batteries : Smoke Emitters : WaterJel Fire Blankets


Fire Projects - Detection Systems

Project: Valima Gardens Retirement Village
Project Date: September 2005
Project Category - Medium Value Up To $200k


Synopsis

Fire Panel: Firenet Addressable.
Field Equipment: Addressable Hochiki detectors, Flashni Sounders in common areas, Hochiki Squashi Sounders in Rooms, Firenet Mimic Panel.

System Design
The system was designed for early warning in both residents rooms and common areas. Due to the age of residents, the client wanted as minimal duress to the clients in the event of the fire panel in alarm.

The panel was designed, if it detected an alarm in a room it would sound the squashni sounder base in the room alerting or waking the resident as well as notifying the local fire brigade. At the same time it would operate the fire doors and notify staff on the Mimic Panel so they did not have to run to the main Fire Panel.

In the event that a fire was detected in a common area "corridors" all common Flashni will sound along with all sounder bases in the rooms. Thus alerting all to evacuate.

In addition the main fire panel located in the existing building was a conventional type which we upgraded also to a Firenet Panel we designed that panel with convention card to pick up existing field equipment. By completing this we were able to network the two Main Firenet fire Panels allowing the staff in the existing building to see and monitor what was happening in the adjacent building.

The system was given it's own Fire Brigade transponder unit to allow the Fire Service to gain prior knowledge to which building was in alarm.


Firenet panel installed with LCD blue screen, panel is locked down with system operator keys.


Firenet Mimic panel was provided on the first floor, the mimic allows staff to view what the fire panel
is displaying with out racing down to the main fire panel.


The common area passages


Hochiki smoke detector and sounder bases were provided to keep a slim line ergonomic look through out the building.

 

Project: Paradise Community Church
Project Date: April 2006
Project Category - Medium Value Up To $200k

Churches Web Site: www.paradise.asn.au


Synopsis

Fire Panel: Ampac Addressable FireFinder.
Field Equipment: Ampac Addressable Fire Finder panel, Ampac FastSense smoke sampling system, Addressable Apollo detectors, Vantage Sounders in common areas.

The system was design and installed to give the client an early warning system over a large open space. The challenge to Fire System Services was the vast amount of and different type of usages the auditorium is subject to.
An early warning air sampling system was provided for the auditorium with a remote indicator allowing the venue operators to view what level of sensitivity the system is running at before they isolate or de isolate zones.

Addressable smoke and thermal detectors were provided through out the church offices, workshops and amenities.

With minimal training the staff are able to manage the fire detection system quite adequately.

Two addressable fire panels were provided, one located on stage and one located at the main entrance, allowing staff to quickly locate and assess any incidents that may arise during any services.


Ampac addressable Firefinder fire panel, installed with LCD green screen.


Common Area Passage Hallway
Red Combo - Audio Visuals
White - Apollo Smoke Detectors


Main Auditorium
Protected by Fastsense Air Sampling System

As you can see the fastsense creates a extremely slim line system, as the sampling points (as seen on the right), sit flush with the ceiling line.

Fastsense Air Sampling System


Fastsense Panel


Fastsense Remote Indicator


click on to email us