The list below covers Building Code of Australia (BCA) & Australian Standards 1851- 2005 Maintenance of Fire Protection Systems and Equipment, together with servicing frequency requirements.
AUTOMATIC FIRE SPRINKLER SYSTEM
- section 2
Automatic fire suppression (sprinkler)
Automatic sprinkler systems are inspected and tested in accordance with AS1851
Section 2 on a weekly basis.
Additionally, a log book is required to be placed at the location of the sprinkler
in order for the technician to record the results of each inspection, in accordance
with AS1851 Section 2.
Wall wetting sprinkler and drencher
systems
Wall wetting and drencher systems are inspected and tested in accordance with
AS1851 Section 2 on an weekly basis.
AS2.4.7 12 heads or less on a monthly basis.
FIRE PUMPSETS - section 3
Electric & Diesel Pumps
Fire hydrant booster pumps are inspected in accordance to 1851 section 3 on
a weekly basis.
Additionally, in the case of a hydrant booster pump being present, a log book
is required in order for the technician to record the results of each weekly
inspection, in accordance with maintenance code AS1851 Section 3.
FIRE HYDRANT SYSTEMS - section
4
Fire Hydrant System
Fire hydrants are inspected and tested in accordance
with AS 1851 section 4 on an six monthly basis.
Every year unassisted flow test is required.
Hydrant Boosters, Every year unassisted flow test is required. Every five an
assisted flow test is required.
DELIVERY LAY FLAT FIRE HOSE -
section 5
Lay Flat Fire Hose
Delivery lay flat fire hoses
are
inspected
and
tested in accordance
with AS 1851 section 5 on a yearly basis.
FIRE DETECTION SYSTEMS - section
6
Automatic fire detection and alarm system
Automatic fire detection and alarm systems (panels) are inspected and tested
in accordance with AS1670 & AS1851 Section 6 on a monthly
basis.
Additionally, a log book is required to be placed at the location of the fire
indicator panel in order for the technician to record the results of each inspection,
in accordance with AS1851 Section 6.
SMOKE ALARMS AND HEAT ALARMS -
section 7
Smoke and heat detectors
Back to Panel - Smoke and heat detectors are inspected
and tested in accordance with AS1851 Section 7 on an yearly
basis.
240 Volt - Smoke and heat detectors are inspected
and tested in accordance with AS1851 Section 7 on an six
monthly basis.
FIRE ALARM MONITORING SYSTEMS
- section 8
Alarm Monitoring
Alarm monitoring is
inspected
and
tested in accordance
with AS 1851 section 8 on a yearly basis.
SOUND SYSTEMS FOR EMERGENCY PURPOSES
- section 9
Audio Visual Devices
Sound
Systems inspected
and
tested in accordance
with AS 1851 section 9 on a monthly basis.
INTERCOM SYSTEMS FOR EMERGENCY
PURPOSES - section 10
Emergency Warning and Intercommunication
system
Emergency Warning and Intercommunication Systems
(EWIS) are tested in accordance with AS1851 Section 10 on a
six
monthly
basis.
GASEOUS FIRE EXTINGUISHING SYSTEMS
- section 11
Gas Dump Systems
Gas fire extinguishing
systems
are inspected & tested in
accordance
with
AS1851
Section 11 on a
monthly
basis.
FIXED AEROSOL FIRE EXTINGUISHING
SYSTEMS - section 12
Aerosol Dump Systems
Aerosol
fire extinguishing
systems
are inspected & tested in accordance with AS1851 Section 12 on a
monthly
basis.
OPEN NOZZLE WATER MIST FIRE EXTINGUISHING
SYSTEMS - section 13
Wet Mist Extinguishing Systems
Wet
mist fire extinguishing
systems
are inspected & tested in accordance with AS1851 Section 13 on a
monthly
basis.
FIRE HOSE REELS - section 14
Fire Hose Reel
Fire hose reel systems are inspected and tested in accordance with AS1851 section
14
on
a six monthly basis.
PORABLE AND WHEELED FIRE EXTINGUISHERS
- section 15
Portable Fire Extinguishers
Portable fire extinguishers are inspected and tested in accordance with AS1851
Section 15 on a six monthly basis.
Additionally, five years pressure testing is required, plus recharging when an
extinguisher is discharged.
FIRE BLANKETS - section 16
Portable fire blankets
Portable fire blankets are inspected
in accordance with AS1851
Section 16 on a six monthly basis.
PASSIVE FIRE AND SMOKE CONTAINMENT
SYSTEMS - section 17
Fire Dampers
Fire dampers are inspected and tested in accordance with AS1851 Section 17 on
an six monthly
basis.
Fire Doors
Fire doors are inspected annually and tested in accordance with AS1851 Section
17 on a three monthly basis.
Fire Walls and Barriers / Separations
Fire walls barriers are inspected and tested
in accordance with AS1851 Section 17 on an six
monthly
basis.
FIRE AND SMOKE CONTROL FEATURES
OF HVAC SYSTEMS - section 18
Mechanical Air Handling System
Mechanical air handling systems are inspected and tested in accordance with AS1851
Section 18 on a three monthly basis.
Pressurizing systems (smoke spill & supply air fans) are inspected and tested
in accordance with AS1851 Section 18 on a three monthly
basis.
EMERGENCY EVACUATION PROCEDURES
- section 19
Emergency Plans & Evac Procedures
Emergency
plans & Evac procedures are inspected in accordance
with AS1851 Section 19 on an monthly
basis.
EGRESS
Paths of travel, Stairways, Passageways or
Ramps
Paths of travel for stairways, passageways and ramps are done in accordance
to BCA D 2.23 on a yearly basis.
Warning and Operational Signs (stairway notices)
Warning and operational signs are inspected in accordance with BCA D 2.23
at the same time that fire doors are inspected and tested on a yearly
basis.
EXIT & EMERGENCY LIGHTING
Exit and Emergency Lighting
Exit and Emergency lights are inspected and tested in accordance with AS2293.2
and AS2293.3 on a six monthly basis.